The Potter PS10 Series Pressure Actuated Switches are designed for the
detection of a waterfl ow condition in automatic fi re sprinkler systems of
particular designs such as wet pipe systems with alarm check valves, dry
pipe, preaction, or deluge valves. The PS10 is also suitable to provide a
low pressure supervisory signal; adjustable between 4 and 15 psi (0,27 and
1,03 BAR).
1. Apply Tefl on tape to the threaded male connection on the device.
(Do not use pipe dope)
2. Device should be mounted in the upright position (threaded connection down).
3. Tighten the device using a wrench on the fl ats on the device.
Wiring Instructions
1. Remove the tamper resistant screw with the special key provided.
2. Carefully place a screwdriver on the edge of the knockout and
sharply apply a force suffi cient to dislodge the knockout plug. See Fig 9
3. Run wires through an approved conduit connector and affi x the connector
to the device.
4. Connect the wires to the appropriate terminal connections for the
service intended. See Figures 2,4,5, and 6. See Fig 7 for two switch, one
conduit wiring.