C. HIGH VELOCITY SPRAY NOZZLE (1 INCH)

TECHNICAL DATA
MODEL HV-HB Brass
HV-H Stainless steel
MAXIMUM WORKING 12 Bar (175 PSI)
PRESSURE
END CONNECTION 1” BSPT
(1” NPT OPTIONAL)
MATERIAL Housing & Scroll
Model HB – Brass IS : 291
(equivalent to ASTM-B21)
Strainer – Copper
Model H – SS 316 (CF8M)
Stainless Steel Housing
Strainer – Stainless steel
INCLUDED WATER SPRAY K-FACTOR
SPRAY ANGLE AND ANGLE METRIC (US)
K-FACTOR 100° – K 48
100° – K 58
75° – K 61
90° – K 78
WEIGHT (Approx) HV-HB Brass 0.25 Kg
HV-H SS 0.22 Kg
FINISH HV-HB Brass Finish
Nickel Chrome
Plated (optional)
HV-H Natural
APPROVALS UL Listed
ORDERING Specify Model, K-Factor,
INFORMATION Spray angle, Finish
and end connection

Description

C. HIGH VELOCITY SPRAY NOZZLE (1 INCH)
C. HIGH VELOCITY SPRAY NOZZLE (1 INCH)

High Velocity Water Spray Nozzles are internal swirl plate type open nozzles designed for use in fixed water spray or deluge system for the fire protection
application. These nozzles produce solid uniform and dense core of high velocity water spray to effect fire control. Nozzles are normally used to cool the surface as well as for extinguishment. Nozzles are typically used for Deluge protection of special hazards such as oil filled transformers, switch-gear, chemical process equipments, conveyor system, diesel engines, flammable liquid storage areas and similar hazards. The minimum desirable pressure to achieve a reasonable spray pattern is 2.1 Kg./sq.cm. (30 psi). The water distribution pattern is as shown in the graph in following pages giving maximum effective axial distance from the nozzle. The spray pattern shown is with indoor application. The system designer must consider wind velocity while designing the system for outdoor application. The spray pattern is drawn considering maximum of 20 Km/hr. Field obstruction if any affecting the spray pattern of the nozzle must be considered. The nozzle may be oriented in any position as deemed necessary to cover the hazard.
2.1 bar to 7 bar pressure at Nozzle is recommended for effective application requiring High Velocity Water delivery for rapid extinguishment of all fires by emulsification. The Nozzles are having inbuilt Strainer, but still main pipeline strainer is required in the system. The Blow-off cap can be used to prevent the depositing of foreign material in the water way of the nozzle.Use of Blow-off cap is optional and not UL listed.

MAINTENANCE
The spray nozzle must be handled with due care. For best results , the storage as well as any further shipment be made in original packing only. Nozzle which is visibly damaged should not be installed. Use Teflon tape or soft thread sealant on the male thread of the nozzle. It is recommended that the water spray system be inspected by an authorised technical personnel. The nozzle must be checked for corrosion, external and internal obstruction, blockage if any. The nozzle should be cleaned or replaced if required. The system must be operated with optimum water flow at least three times in a year or as per the provision of NFPA/TAC or local authority having jurisdiction. The owner is solely responsible for maintaining the water spray system and components therein, so that it performs properly when required